Two versions of the thermal magnetic trip unit:
Fixed thermal and magnetic in the Z version.
U version: fixed magnetic and movable thermal.
* Access to the cover's mechanical test button.
MCCB settings are safeguarded with a lockable lid.
* O 4mm integrated padlocking handle
Cage terminals * Complies with BS EN 60947-2 * Connection capacity: 95mm2 for rigid cables, 70mm2 for flexible cables.
Technical Information
Connection cross-sect. flexible cable |
4 / 70mm⊃2; |
Connection cross-sect. rigid cable |
4 / 95mm⊃2; |
Number of modules |
4.5 |
Rated current |
100 A |
Rated operational voltage Ue |
220/415 V |
Tightening torque |
6Nm |
Type of pole |
3P3D |
* Fixed thermal: 1x In
* Adjustable thermal: 0.63 - 0.8 - 1 x In