range |
ComPact
|
|
product name |
ComPact NS
|
|
range of product |
ComPact NS630b…1600
|
|
device short name |
Compact NS1600N
|
|
product or component type |
Circuit breaker
|
|
device application |
Distribution
|
|
Number of poles |
4P
|
|
protected poles description |
4d
|
|
neutral position |
Left
|
|
(In) rated current up to 65 °C |
1600 A at 50 °C
|
|
[Ue] rated operational voltage |
690 V AC 50/60 Hz
|
|
network type |
AC
|
|
network frequency |
50/60 Hz
|
|
suitability for isolation |
Yes conforming to EN/IEC 60947-2
|
|
utilisation category |
Category B
|
|
[Icu] rated ultimate short-circuit breaking capacity |
30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
|
|
Performance level |
N 50 kA 415 V AC
|
|
trip unit name |
Micrologic 2.0
|
|
trip unit technology |
Electronic
|
|
trip unit protection functions |
LI
|
|
control type |
Toggle
Rotary handle
|
|
Circuit breaker mounting mode |
Fixed
|
DATA SHEET LINK