Control Relay

Control Relay

A Control Relay, commonly known as a Relay, is an electromagnetic switch that acts as a switch. Electrical current flows via a conducting coil in a control relay, which opens or closes a switch.

Show All Items

 

Sort By:

Reset

 

Item Code

Product Detail

Unit

QTY

Unit Price

T. Price

Add to Enquiry

ICM401 Three-Phase Line Voltage Monitor Loss Protector

Pcs

AED 297.00

AED 297.00

Brand Name ICM Controls
Colour black
Ean 0800442000145 , 0841999147990
Included Components Control
Model Number ICM401
Number of Items 1
Part Number ICM401
UPC 841999147990 , 800442000145
  • 3-Phase protection for single side
  • Monitors for Phase reversal, Phase loss, unbalance -Percent as a function of input Voltage
  • Bright LED indicators for on and fault
  • Universal 3-phase input: 190-600 VAC
  • Control Voltage: 18-30 VAC

Cash on delivery not available
Returns not allowed
Three Phase Relay - LXPRC/S-4W

Pcs

AED 163.30

AED 163.30

Three Phase Relay - LXPRC/S-4W ( Under & Over Voltage, Phase & Neutral Loss + Sequence )

  • Under and Over voltage monitoring (Window)
  • Monitors own three phase, 4-wire supply
  • Detects incorrect phase sequence, phase and neutral loss
  • Adjustable Trip levels and Time delay
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed

The product monitors it’s own three-phase supply and for the output relay to energise, all phases (and neutral) must be present, the phase sequence correct and the phase to neutral voltages within the set Under/Over trip levels. If any of these conditions are not met, the relay will de-energise.

SPECIFICATION:

  • Monitoring function: Under/Over voltage
  • Monitored supply voltage*: 120V, 127V, 220V, 230V or 240VAC
  • Trip level: Under: 75 – 95%/Over: 105 – 125%
  • Hysteresis: ≈2%
  • Time delay: 0.2 – 10s
  • Output: SPDT 8A @ 250V (AC1)
  • Dimensions(mm): W:17.5 x H:89 x D:66.5

Cash on delivery available
Returns allowed
Three Phase Relay - LXPRC / S

Pcs

AED 149.50

AED 149.50

Three Phase Relay - LXPRC / S ( Under & Over Voltage, Phase Loss + Sequence )

  • Under and Over voltage monitoring (Window)
  • Monitors own three phase, 3-wire supply
  • Detects incorrect phase sequence and phase loss
  • Adjustable Trip levels and Time delay
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed

The product monitors it’s own three-phase supply and for the output relay to energise, all phases must be present, the phase sequence correct and the phase to phase voltages within the set Under/Over trip levels. If any of these conditions are not met, the relay will de-energise.

SPECIFICATION:

  • Monitoring function: Under/Over voltage
  • Monitored supply voltage*: 110V, 208V, 380V, 400V or 415VAC
  • Trip level: Under: 75 – 95%/Over: 105 – 125%
  • Hysteresis: ≈2%
  • Time delay: 0.2 – 10s
  • Output: SPDT 8A @ 250V (AC1)
  • Dimensions(mm): W:17.5 x H:89 x D:66.5

Cash on delivery available
Returns allowed
Control Relay - LXCVR ( Under and Over Voltage )

Pcs

AED 149.50

AED 149.50

Control Relay - LXCVR ( Under and Over Voltage )

  • Under and Over voltage monitoring (Window)
  • Monitors own supply
  • Adjustable Trip levels
  • Adjustable Time delay
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed

When power is applied, the output relay will energise provided the monitored supply voltage is above the set Under voltage trip level and below the set Over voltage trip level.

Under voltage:
If the voltage decreases below the set Under voltage trip level, the relay will de-energise. The voltage must increase above the trip level plus the set hysteresis setting before the relay will re-energise.

Over voltage:
If the voltage increases above the set Over voltage trip level, the relay will de-energise. The voltage must decrease below the trip level minus the set hysteresis setting before the relay will re-energise.

SPECIFICATION:

  • Monitoring function: Under/Over voltage
  • Monitored supply voltage*: 110V, 115V, 220V, 230V or 240V AC 48-63Hz
  • Trip level: Under: 75 – 95%/Over: 105 – 125%
  • Hysteresis: ≈2%
  • Time delay: 0.2 – 10s
  • Output: SPDT 8A @ 250V (AC1)
  • Dimensions(mm): W:17.5 x H:89 x D:66.5

 

Cash on delivery available
Returns allowed
Control Relay - LMWVR

Pcs

AED 333.50

AED 333.50

Control Relay - LMWVR ( Multifunction Windowed Voltage Monitoring )

  • Under and Over voltage monitoring (Window)
  • 7 Selectable nominal voltages (12V, 24V, 48V, 110V, 115V, 230V or 240V)
  • Adjustable Trip levels
  • Adjustable Time delay
  • Isolated Auxiliary supply
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed

The product is designed to monitor a nominal voltage on a separate supply and ensure it stays within the set limits. An auxiliary supply (required to power the unit) must be present for the product to function. When the monitored voltage is applied the relay will energise.

Under voltage: If the monitored voltage decreases below the set Under voltage trip level, the relay will de-energise. The voltage must increase above the trip level plus the set hysteresis setting before the relay will re-energise.

Over voltage: If the monitored voltage increases above the set Over voltage trip level, the relay will de-energise. The voltage must decrease below the trip level minus the set hysteresis setting before the relay will re-energise.

SPECIFICATION:

  • Monitoring function: Under and Over voltage
  • Monitored nominal voltages : 12V, 24V, 48V, 110V, 115V, 230V or 240V AC/DC
  • Trip level: Under: 70 – 90%/Over: 105 – 130% (of selected nominal voltage)
  • Hysteresis: ≈2%
  • Time delay: 0.1 – 30s
  • Aux. supply voltage*: 12 – 60V AC/DC or 24 – 230V AC/DC
  • Output: SPDT 8A @ 250V (AC1)
  • Dimensions(mm): W:17.5 x H:89 x D:66.5

Cash on delivery available
Returns allowed
Control Relay - LMCVR / 500V

Pcs

AED 333.50

AED 333.50

Control Relay - LMCVR / 500V ( Multifunction, Combined Voltage Monitoring )

  • Under or Over voltage monitoring (selectable)
  • 5 Selectable voltage ranges (20V, 50V, 100V, 200V or 500V)
  • Adjustable Trip level, Hysteresis and Time delay + Latch
  • Isolated Auxiliary supply
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed

The product is designed to monitor voltage across a load (for example). An auxiliary supply (required to power the unit) must be present for the product to function.

Two monitoring modes available:

Under voltage:
In normal operation, the relay is in the energised state (monitored voltage above the set trip level). When the voltage decreases below the trip level, the relay will de-energise after the set delay. The voltage must increase above the trip level plus the hysteresis before the relay will re-energise.

Over voltage:
In normal operation, the relay is in the energised state (monitored voltage below the set trip level). When the voltage increases above the trip level, the relay will de-energise after the set delay. The voltage must decrease below the trip level minus the hysteresis before the relay will re-energise.

SPECIFICATION:

  • Monitoring function: Under or Over voltage
  • Monitored voltage ranges: 2 – 20V, 5 – 50V, 10 – 100V, 20 – 200V or 50 – 500V AC/DC
  • Trip level: 10 – 100% of selected range
  • Hysteresis: 2 or 10%
  • Time delay: 0.1 – 30s
  • Aux. supply voltage*: 12 – 60V AC/DC or 24 – 230V AC/DC
  • Output: SPDT 8A @ 250V (AC1)
  • Dimensions(mm): W:17.5 x H:89 x D:66.5

Cash on delivery available
Returns allowed
Control Relay - LMCVR / 20V

Pcs

AED 333.50

AED 333.50

Control Relay - LMCVR / 20V ( Multifunction, Combined Voltage Monitoring )

 

  • Under or Over voltage monitoring (selectable)
  • 5 Selectable voltage ranges (1V, 2V, 5V, 10V or 20V)
  • Adjustable Trip level, Hysteresis and Time delay + Latch
  • Isolated Auxiliary supply
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed

The product is designed to monitor voltage across a load (for example). An auxiliary supply (required to power the unit) must be present for the product to function.

Two monitoring modes available:

Under voltage:
In normal operation, the relay is in the energised state (monitored voltage above the set trip level). When the voltage decreases below the trip level, the relay will de-energise after the set delay. The voltage must increase above the trip level plus the hysteresis before the relay will re-energise.

Over voltage:
In normal operation, the relay is in the energised state (monitored voltage below the set trip level). When the voltage increases above the trip level, the relay will de-energise after the set delay. The voltage must decrease below the trip level minus the hysteresis before the relay will re-energise.

SPECIFICATION:

  • Monitoring function: Under or Over voltage
  • Monitored voltage ranges: 0.1 – 1V, 0.2 – 2V, 0.5 – 5V, 1 – 10V or 2 – 20V AC/DC
  • Trip level: 10 – 100% of selected range
  • Hysteresis: 2 or 10%
  • Time delay: 0.1 – 30s
  • Aux. supply voltage*: 12 – 60V AC/DC or 24 – 230V AC/DC
  • Output: SPDT 8A @ 250V (AC1)
  • Dimensions(mm): W:17.5 x H:89 x D:66.5

Cash on delivery available
Returns allowed
Control Relay - LBVR / A ( Battery Voltage Monitoring )

Pcs

AED 172.80

AED 172.80

Control Relay - LBVR / A ( Battery Voltage Monitoring )

  • Under voltage monitoring in battery applications
  • Monitors own supply
  • Adjustable Trip level
  • Adjustable Time delay
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed

When power is applied, the output relay will energise if the monitored voltage is above the set trip level. When the voltage decreases below the set trip level the relay will de-energise after the set time delay period. The voltage must then increase above the trip level and plus the hysteresis setting before it will energise again.

SPECIFICATION:

  • Monitoring function: Under voltage
  • Supply voltage: 12 – 24V DC
  • Trip level: 9 – 28V DC
  • Hysteresis: 5% (fixed)
  • Time delay: 1 – 30s
  • Output: SPDT 8A @ 250V (AC1)
  • Dimensions(mm): W:17.5 x H:89 x D:66.5

Cash on delivery available
Returns allowed
Control Relay - LMCCR-10A

Pcs

AED 270.00

AED 270.00

Control Relay - LMCCR-10A ( Multifunction, Combined Current Monitoring )

  • Under or Over current monitoring (selectable)
  • 3 Selectable current ranges (2A, 5A or 10A)
  • Adjustable Trip level, Hysteresis and Time delay + Latch
  • Isolated Auxiliary supply
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed

The product is designed to monitor current in a feed to a load. An auxiliary supply (required to power the unit) must be present for the product to function.

Two monitoring modes available:

Under current:
In normal operation, the relay is in the energised state (monitored current above the set trip level). When the current decreases below the trip level, the relay will de-energise after the set delay. The current must increase above the trip level plus the hysteresis before the relay will re-energise.

Over current:
In normal operation, the relay is in the energised state (monitored current below the set trip level). When the current increases above the trip level, the relay will de-energise after the set delay. The current must decrease below the trip level minus the hysteresis before the relay will re-energise.

SPECIFICATION:

  • Monitoring function: Under or Over current
  • Monitored current ranges: 0.2 – 2A, 0.5 – 5A or 1 – 10A AC/DC
  • Trip level: 10 – 100% of selected range
  • Hysteresis: 2 or 10%
  • Time delay: 0.1 – 30s
  • Aux. supply voltage*: 12 – 60V AC/DC or 24 – 230V AC/DC
  • Output: SPDT 8A @ 250V (AC1)
  • Dimensions(mm): W:17.5 x H:89 x D:66.5

Cash on delivery available
Returns allowed
Control Relays - LMCCR-2A

Pcs

AED 270.00

AED 270.00

Control Relay - LMCCR-2A ( Multifunction, Combined Current Monitoring )

  • Under or Over current monitoring (selectable)
  • 3 Selectable current ranges (0.2A, 1A or 2A)
  • Adjustable Trip level, Hysteresis and Time delay + Latch
  • Isolated Auxiliary supply
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed

The product is designed to monitor current in a feed to a load. An auxiliary supply (required to power the unit) must be present for the product to function.

Two monitoring modes available:

Under current:
In normal operation, the relay is in the energised state (monitored current above the set trip level). When the current decreases below the trip level, the relay will de-energise after the set delay. The current must increase above the trip level plus the hysteresis before the relay will re-energise.

Over current:
In normal operation, the relay is in the energised state (monitored current below the set trip level). When the current increases above the trip level, the relay will de-energise after the set delay. The current must decrease below the trip level minus the hysteresis before the relay will re-energise.

SPECIFICATION:

  • Monitoring function: Under or Over current
  • Monitored current ranges: 0.02 – 0.2A, 0.1 – 1A or 0.2 – 2A AC/DC
  • Trip level: 10 – 100% of selected range
  • Hysteresis: 2 or 10%
  • Time delay: 0.1 – 30s
  • Aux. supply voltage*: 12 – 60V AC/DC or 24 – 230V AC/DC
  • Output: SPDT 8A @ 250V (AC1)
  • Dimensions(mm): W:17.5 x H:89 x D:66.5

Cash on delivery available
Returns allowed






















Join Our Newsletter Now

Get E-mail updates about our latest shop and special offers.

Address: GooXoom.com
Salah Al Din Street
Deira, Dubai
United Arab Emirates

Phone: +971522074931

Email: support@gooxoom.com