SIRIUS Circuit Breaker | Size S00 | Motor Protection | CLASS 10
General Information
| Parameter |
Value |
| Brand |
SIRIUS (Siemens) |
| Product Type |
Circuit Breaker for Motor Protection |
| Type Designation |
3RV2 |
| Frame Size |
S00 |
| Compatible Contactor Size |
S00, S0 |
| Auxiliary Switch Extension |
Yes |
| Net Weight |
349 g |
⚡ Electrical Ratings (Main Circuit)
| Parameter |
Value |
| No. of Poles |
3 |
| Adjustable Overload Range |
2.2 – 3.2 A |
| Rated Operational Current |
3.2 A |
| Operating Voltage Range |
20 – 690 V AC |
| Insulation Voltage |
690 V |
| Surge Voltage Resistance |
6 kV |
| Operating Frequency |
50 – 60 Hz |
| Max. Operating Frequency |
15 operations/hour |
Motor Power Ratings (AC-3 & AC-3e)
| Voltage |
Power |
| 230 V |
0.6 kW |
| 400 V |
1.1 kW |
| 500 V |
1.5 kW |
| 690 V |
2.2 kW |
Protection Functions
| Parameter |
Value |
| Trip Class |
CLASS 10 |
| Overload Release Type |
Thermal |
| Short-Circuit Trip Type |
Magnetic (Instantaneous) |
| Instantaneous Trip Current (N-Release) |
42 A |
| Phase Failure Detection |
✅ Yes |
| Ground Fault Detection |
❌ No |
Short-Circuit Breaking Capacity (Icu / Ics)
| Voltage |
Breaking Capacity |
| 240 V |
100 kA |
| 400 V |
100 kA |
| 500 V |
100 kA |
| 690 V |
10 kA |
UL/CSA Ratings
| Parameter |
Value |
| FLA at 480 V (3-phase) |
3.2 A |
| FLA at 600 V (3-phase) |
3.2 A |
| Motor HP — 110/120 V (1-phase) |
0.1 hp |
| Motor HP — 230 V (1-phase) |
0.25 hp |
| Motor HP — 200/208 V (3-phase) |
0.5 hp |
| Motor HP — 460/480 V (3-phase) |
2 hp |
| Motor HP — 575/600 V (3-phase) |
2 hp |
| CCN |
E156943 (NKJH, NKJH7) |
Ambient Conditions
| Parameter |
Value |
| Operating Temperature |
-20°C to +60°C |
| Storage Temperature |
-50°C to +80°C |
| Relative Humidity (Operation) |
10 – 95% |
| Max. Installation Altitude |
2,000 m above sea level |
Dimensions & Mounting
| Parameter |
Value |
| Height |
97 mm |
| Width |
45 mm |
| Depth |
97 mm |
| Mounting |
Screw or 35 mm DIN Rail (EN 60715) |
| Mounting Position |
Any |
| Side-by-Side Spacing |
0 mm |
Connections & Terminals
| Parameter |
Value |
| Connection Type |
Screw-type terminals |
| Conductor (Solid/Stranded) |
2× (0.75–2.5 mm⊃2;), 2× 4 mm⊃2; |
| Conductor (Fine-stranded) |
2× (0.5–1.5 mm⊃2;), 2× (0.75–2.5 mm⊃2;) |
| AWG Cable Size |
2× (18–14 AWG), 2× 12 AWG |
| Tightening Torque |
0.8 – 1.2 N·m |
| Screw Thread |
M3 |
| Screwdriver |
Pozidriv Size 2, Ø 5–6 mm |
Safety Data
| Parameter |
Value |
| IP Rating (Front) |
IP20 |
| Touch Protection |
Finger-safe |
| Safety Switching OFF |
✅ Yes |
| Safety Switching ON |
❌ No |
| Max. Service Life |
10 years |
| ISO 13849 Device Type |
Type 3 |
| IEC 61508 Safety Device Type |
Type A |
| Mechanical Life (Main & Aux. Contacts) |
100,000 cycles |
| Electrical Endurance |
100,000 cycles |
| Shock Resistance (IEC 60068-2-27) |
25g / 11 ms |
Environmental (CO₂ Footprint)
| Phase |
CO₂ Equivalent |
| Manufacturing |
1.98 kg |
| Logistics/Sales |
0.134 kg |
| Operation (lifetime) |
72.7 kg |
| End of Life |
-0.116 kg |
| Total |
74.698 kg |
✅ Certifications & Approvals
- Hazardous Locations Approved
- Maritime Application Certified
- Railway Confirmed
- IEC, UL/CSA Listed